When you are a data center manager or consulting-specifying engineer, very few things are more unsettling than the unexpected. We hope this list helps IT and engineering professionals better anticipate these issues and prepares them with the appropriate technologies, solutions, and best practices.
Generally speaking we have 10 advice for your data center:
High-density predictions finally come true
After rapid growth early in the century, projections of double-digit rack densities have been slow to come to fruition. Average densities hovered between 6.0 and 7.4 kW per rack from 2006 to 2009, but the most recent Data Center Users’ Group (DCUG) survey predicted average rack densities will reach 12.0 kW within three years. That puts a premium on adequate UPS capacity and power distribution as well as cooling to handle the corresponding heat output.
Servers may be replaced three times before UPS or cooling systems renewal
Server refreshes happen approximately every three years. Cooling and UPS systems are expected to last much longer—sometimes decades. That means the infrastructure that organizations invest in today must be able to support—or, more accurately, scale to support—servers that may be two, three, or even four generations removed from today’s models. Modular solutions can scale to meet both short- and long-term requirements. Engineers will need to consider and make the necessary adjustments and allocations regarding day-to-day servicing and maintenance of the longer lasting power and cooling equipment.
Down time is expensive
We don't want it. The most common causes of downtime are UPS battery failure and exceeding UPS capacity. Avoid those problems by investing in the right UPS—adequately sized to support the load—and proactively monitoring and maintaining batteries. This gives engineers an opportunity to share best practices with clients and recommend battery monitoring solutions and high-end availability architecture. They can use the cost of downtime information to support recommendations and ensure clients understand how they can implement design changes and modifications that will improve availability.
Energy rebates are available for energy efficiency upgrades
Many utility providers offer energy rebates and incentives for data centers that make energy efficiency improvements. This presents an opportunity for engineers to propose high-efficiency designs and help clients receive reimbursements for upgrading legacy equipment with high-efficiency power and cooling systems. Clients may also look to engineers to assist with the often lengthy application process. Once the reimbursement has been approved, utilities will request information on actual project costs and may require follow-up measurement and verification to determine actual energy savings.
Industry codes are playing a larger role in cooling strategy
In the 2010 edition of ASHRAE 90.1: Energy Standard for Buildings Except Low-Rise Residential Buildings, the SCOP (seasonal coefficient of performance) rating was expanded to include data centers. Codes are becoming more numerous and impacting data center cooling strategies and technology developments. It is important that engineers keep abreast of new codes and regulations and the latest technologies that enable compliance.
Monitoring can be a mess
IT managers have more visibility into their data centers than ever before, but accessing and making sense of the data that comes with that visibility can be a daunting task. According to an Emerson Network Power survey of data center professionals, data center managers use, on average, at least four different software platforms to manage their physical infrastructure. Of those surveyed, 41% say they produce three or more reports for their supervisors every month, and 34% say it takes three hours or more to prepare those reports. The solution? Move toward a single monitoring and management platform that can consolidate that information and proactively manage the infrastructure to improve energy and operational efficiency, and even availability.
IT Person may be in charge of the building’s HVAC system
The gap between IT and facilities is shrinking. Traditionally, IT and data center managers have had to work through facilities when they needed more power or cooling to support increasing IT needs. That process is being streamlined. For engineers, it is important that they now incorporate all of these players into the design process. Gone are the days when the engineer had to work with only one or two individuals, usually from the facility side. Now it is a complex ecosystem comprised of IT, operations, facilities, and sometimes procurement.
That patchwork data center needs to be a quilt
In the past, data center managers and engineers freely mixed and matched components from various vendors because those systems worked together only tangentially. However, the advent of increasingly intelligent, dynamic infrastructure technologies and monitoring and management systems has increased the amount of actionable data across the data center, delivering real-time modeling capabilities that enable significant operational efficiency. IT and infrastructure systems still can work independently, but to truly leverage the full extent of their capabilities, integration is imperative.
Data center on demand is a reality
The days of lengthy design, order and deployment delays are over. Today there are modular, integrated, rapidly deployable data center solutions for any space. Integrated, virtually plug-and-play solutions that include rack, server, and power and cooling can be installed easily in a closet or conference room. On the larger end, containerized data centers can be used to quickly establish a network or to add capacity to an existing data center.
IT loads vary a lot
Many industries see extreme peaks and valleys in their network usage. Financial institutions, for example, may see heavy use during traditional business hours and virtually nothing overnight. Holiday shopping and tax seasons also can create unusual spikes in IT activity. Businesses depending on their IT systems during these times need to have the capacity to handle those peaks but often operate inefficiently during the valleys. A scalable infrastructure with intelligent controls can adjust to those highs and lows to ensure efficient operation.
About SMA
Strategic Media Asia (SMA) is one of the CPD Course Providers of the Chartered Institution of Building Services Engineers (CIBSE).
SMA, a critical infrastructure training and event organizer based in Hong Kong, provides an interactive environment and opportunities for members of IDC industry and engineers to exchange professional views and experience on critical infrastructure and E&M facilities.
For details of other data center courses and seminars, please visit our website at http://www.stmedia-asia.com/trainings.html.
Best Practices for Critical Facilities Design, Efficiency and Operations
Wednesday, October 15, 2014
10 Recommendations for your Data Center
Labels:
ASHRAE,
Cooling System,
Data Center,
down time,
HVAC,
IT Load,
Modular,
SMA,
Strategic Media Asia,
UPS
Location:
Hong Kong
Thursday, October 9, 2014
(Reminder) IXTech Solutions Day 2014
IXTech Solutions Day 2014 - The Demands of Ecosystem in the Dynamic World
You are cordially invited to attend this event in Hong Kong. Online registration is available at http://goo.gl/vva4Ao
Date: November 19, 2014 (Wednesday)
Time: 09:30 to 17:00
Venue: Conference Hall, HKPC Building, 78 Tat Chee Avenue, Kowloon Tong, Hong Kong
For details, please visit http://green-data.blogspot.hk/2014/09/ixtech-solutions-day.html
You are cordially invited to attend this event in Hong Kong. Online registration is available at http://goo.gl/vva4Ao
Date: November 19, 2014 (Wednesday)
Time: 09:30 to 17:00
Venue: Conference Hall, HKPC Building, 78 Tat Chee Avenue, Kowloon Tong, Hong Kong
For details, please visit http://green-data.blogspot.hk/2014/09/ixtech-solutions-day.html
Location:
Hong Kong
Thursday, September 25, 2014
Site Maintenance - www.stmedia-asia.com
Thanks for your continuous support and interest in our content in critical facilities.
Kindly note that our website, www.stmedia-asia.com, was scheduled maintenance between 23 - 25 September 2014. During that period, the site or any linked content for this blog may be unable to display or response properly.
The site will be resumed as soon as possible. We apologies for any inconvenience caused.
Monday, September 22, 2014
Invitation to Data Center Technical Visit (2 Sites) + CPD Course in Critical Facilities and Data Center Design
2-days CPD Course in Data Center Facilities Design and Infrastructure Engineering (23 - 24 October 2014)
(HKIE CPD Course Code: CPD1029)
The course is designed for Building Services Engineers, Facilities / Data Center Managers, IT Management, etc. to enrich and update the knowledge in critical facilities and data centers design & build. It is more than a general introductory program for data center. Topics include:
- IT strategy
- Cabinet layout
- Raised floor system
- Cabinet layout
- Raised floor system
- Data center network and structure
- Telecommunication backbones, redundancy, sizing and planning
- Fiber and optical system design
- Fiber and optical cable components
- Copper cabling components
- Copper system design and high speed ethernet
- Cable distribution, layout and management
- Earthing / grounding and bounding
- Telecommunication backbones, redundancy, sizing and planning
- Fiber and optical system design
- Fiber and optical cable components
- Copper cabling components
- Copper system design and high speed ethernet
- Cable distribution, layout and management
- Earthing / grounding and bounding
- Power (1) – high / low voltage system, switch system, etc.
- Power (2) – UPS, transformers, fuel tanks, generators, etc.
- Cooling (1) – cooling topology, hot / cold aisle, etc.
- Cooling (2) – chiller, CRAC, cooling towers, etc.
- Environmental management system
- Physical security
- Fire protection system
- Physical security
- Fire protection system
Date: 23 - 24 October 2014 (Thursday - Friday)
Time: 10:00 – 18:00 (14 Hours)
Venue: 20/F, New Victory House, 93 - 103 Wing Lok Street, Sheung Wan, Hong Kong
(Very Near Exit A2, Sheung Wan MTR Station)
Fee: Special rate for HKIE's all membership classes
For details and syllabus, please refer to the CPD Course Calendar of Hong Kong Institution of Engineers, HKIE (http://www.hkie.org.hk/eng/html/cpd/cpdviewer.asp?sn=3248).
Kindly complete and return an Application Form together with a crossed cheque made payable to “Strategic Media Asia Limited” - Room 1605, 16/F, Causeway Bay Plaza 1, 489 Hennessy Road, Causeway Bay, Hong Kong.
Sponsored by IXTech (www.hkcix.com) and HKCOLO (www.hkcolo.net)
Further to the critical facilities course, a half-day technical visit is targeted to provide an interactive environment and opportunities for members of IDC industry to exchange professional views and experience on TWO data center facilities (Tier II and Tier III+) and services.
Date: 8 October 2014 (Wednesday)
Duration: 13:45 - 18:00
Assembly Time: 13:45 - 14:00
Assembly Point: Exit D, Kwai Fong MTR Station (Kwai Yan Road, Next to the Bus Stop)
Duration: 13:45 - 18:00
Assembly Time: 13:45 - 14:00
Assembly Point: Exit D, Kwai Fong MTR Station (Kwai Yan Road, Next to the Bus Stop)
Fee: HK$100, Round-trip transportation will be provided
(Waiver for the 2-day CPD course's participants)
(Waiver for the 2-day CPD course's participants)
For details of the technical visit, please visit
Labels:
Cabinet Layout,
Cable Distribution,
Chiller,
Cooling,
CRAC,
Data Center Facilities Design,
Earthing,
Generator,
HKCOLO,
IXTech,
Raised Floor System,
Redundancy,
Technical Visit,
Tier II,
Tier III,
Transformer,
UPS
Location:
Hong Kong
Friday, September 19, 2014
IXTech Solutions Day 2014 - The Demands of Ecosystem in the Dynamic World
We are pleased to announce SMA, a critical facilities and data center training organizer in Hong Kong, becomes one of the sponsors and supporting organizations for the conference - IXTech Solutions Day 2014 - The Demands of Ecosystem in the Dynamic World.
You are cordially invited to join the event in November 2014:
Date: November 19, 2014 (Wednesday)
Time: 09:30 to 17:00
Venue: Conference Hall of Hong Kong Productivity Council (HKPC)
Potential number of visitors: 250
Online Registration is available at http://goo.gl/vva4Ao
For details, please call (852) 2777 5432 or email to event@hkcix.com.
About SMA
Strategic Media Asia (SMA) is one of the CPD Course Providers of the Chartered Institution of Building Services Engineers (CIBSE).
SMA, a critical infrastructure training and event organizer based in Hong Kong, provides an interactive environment and opportunities for members of IDC industry and engineers to exchange professional views and experience on critical infrastructure and E&M facilities.
For details of other data center courses and seminars, please visit our website at http://www.stmedia-asia.com/trainings.html.
You are cordially invited to join the event in November 2014:
Date: November 19, 2014 (Wednesday)
Time: 09:30 to 17:00
Venue: Conference Hall of Hong Kong Productivity Council (HKPC)
Potential number of visitors: 250
Online Registration is available at http://goo.gl/vva4Ao
For details, please call (852) 2777 5432 or email to event@hkcix.com.
About SMA
Strategic Media Asia (SMA) is one of the CPD Course Providers of the Chartered Institution of Building Services Engineers (CIBSE).
SMA, a critical infrastructure training and event organizer based in Hong Kong, provides an interactive environment and opportunities for members of IDC industry and engineers to exchange professional views and experience on critical infrastructure and E&M facilities.
For details of other data center courses and seminars, please visit our website at http://www.stmedia-asia.com/trainings.html.
Location:
Hong Kong
Wednesday, September 10, 2014
More about Data Center Tier Levels
You may refer to our previous discussion about Data Center Uptime and Tier Levels:
http://green-data.blogspot.com/2014/07/data-center-tier-levels-and-uptime.html
Let's evaluate the configuration of critical system / supply with the diagrams:
Tier I
Components capacity to support IT load is 100%
Single distribution path
Rack power < 1kW Multi-points of failure and human errors
Schedule maintenance twice per annum last for 12 hours
Availability 99.67%, annual down time max. 28.8 hours

Tier II
Components capacity to support IT load is N+1
Redundant for critical components
Single distribution path
Rack power < 2kW
Multi-points of failure and human errors
Schedule maintenance 3 times every 2 years each 12 hours
Availability 99.75%, annual down time max. 22 hours

Tier III
Components capacity to support IT load is N+1
Redundant for all components and distribution path
Allow concurrent maintenance
Rack power > 3kW
Require MV supply (11kV in Hong Kong)
Some failure points and human errors
Schedule maintenance not required
Availability 99.98%, annual down time max. 96 mins (Depends on the Situation)

Tier IV
Components capacity to support IT load is N after any failure
Dual active distribution path
No Single Point of Failure
Rack power > 4kW
Require MV supply (11kV in Hong Kong)
Fault Tolerant, Fire, EPO and human errors
Schedule maintenance not required
Availability 99.99%, annual down time max. 48 mins (Depends on the Situation)

The Blogger
Strategic Media Asia (SMA) is one of the CPD Course Providers of the Chartered Institution of Building Services Engineers (CIBSE).
SMA, a critical infrastructure training and event organizer based in Hong Kong, provides an interactive environment and opportunities for members of IDC industry and engineers to exchange professional views and experience on critical infrastructure and E&M facilities.
For details of other data center courses and seminars, please visit our website at http://www.stmedia-asia.com/trainings.html.
http://green-data.blogspot.com/2014/07/data-center-tier-levels-and-uptime.html
Let's evaluate the configuration of critical system / supply with the diagrams:
Tier I
Components capacity to support IT load is 100%
Single distribution path
Rack power < 1kW Multi-points of failure and human errors
Schedule maintenance twice per annum last for 12 hours
Availability 99.67%, annual down time max. 28.8 hours

Tier II
Components capacity to support IT load is N+1
Redundant for critical components
Single distribution path
Rack power < 2kW
Multi-points of failure and human errors
Schedule maintenance 3 times every 2 years each 12 hours
Availability 99.75%, annual down time max. 22 hours

Tier III
Components capacity to support IT load is N+1
Redundant for all components and distribution path
Allow concurrent maintenance
Rack power > 3kW
Require MV supply (11kV in Hong Kong)
Some failure points and human errors
Schedule maintenance not required
Availability 99.98%, annual down time max. 96 mins (Depends on the Situation)

Tier IV
Components capacity to support IT load is N after any failure
Dual active distribution path
No Single Point of Failure
Rack power > 4kW
Require MV supply (11kV in Hong Kong)
Fault Tolerant, Fire, EPO and human errors
Schedule maintenance not required
Availability 99.99%, annual down time max. 48 mins (Depends on the Situation)

The Blogger
Strategic Media Asia (SMA) is one of the CPD Course Providers of the Chartered Institution of Building Services Engineers (CIBSE).
SMA, a critical infrastructure training and event organizer based in Hong Kong, provides an interactive environment and opportunities for members of IDC industry and engineers to exchange professional views and experience on critical infrastructure and E&M facilities.
For details of other data center courses and seminars, please visit our website at http://www.stmedia-asia.com/trainings.html.
Labels:
Availability,
Data Center,
down time,
Maintenance,
N+1,
Rack Power,
Single Point of Failure,
Tier Levels
Location:
Hong Kong
Monday, August 25, 2014
1 Day Refresher Training / Fundamental Course in Data Center Facilities and Operations
Data centers come in different sizes - whether it's four servers in a closet or hundreds of servers in a building - which provide mission critical functions for enterprises and public services.
We are pleased to announce that a 1-day Refresher Training / Fundamental Course in Data Center Facilities and Operations will be launched in Hong Kong. The course outlines a critical infrastructure system supports a typical data center and the main components facilitate a data center operation. It also introduces the standards of TIA-942, Uptime and Tier Levels.
The training is designed for junior operators, engineers and system administrators to acquire basic knowledge in data center critical facilities, on top of the IT system and daily operations.
- What is Data Center
- Applications of Data Center
- Who are the users
- Users’ expectations
- Inside a Data Center – IT, E&M services, Facilities supports
- Data Center Configurations – Architectural, Structural, MEFPD, Network
- Glossary – Resilience, Tier Levels, Redundancy
- Operating a Data Center
- Loss Prevention
- Maintenance Management
- Facilities Supports – MEFPD (Mechanical, Electrical, Fire, Plumb and Drain) Services
- Specific Requirements for Facilities
- Operations Highlights
- Sustainable Management
- Performance Assessments
DOWNLOAD DETAILED SYLLABUS
For details, please visit http://www.stmedia-asia.com/data-center-facilities-operations.html
About the Organizer
Strategic Media Asia (SMA) is one of the CPD Course Providers of the Chartered Institution of Building Services Engineers (CIBSE).
SMA is a critical infrastructure training, seminar and event organizer for corporations and professionals specialized in data center design & build, E&M facilities, structured cabling system, telecommunication, ICT and financial IT services.
For details of other data center courses and seminars, please visit our website at http://www.stmedia-asia.com/trainings.html.
Labels:
Data Center,
Data Center Course,
Data Center Operations,
facilities,
Redundancy,
Resilience,
Tier Levels
Location:
Hong Kong
Tuesday, August 5, 2014
Invitation to Data Centre World Asia 2014
Date: Wednesday 29th and Thursday 30th October 2014, 9:30am-5pm
Location: Suntec Exhibition Centre, Singapore
Event Website: www.datacentreworldasia.com
Strategic Media Asia (SMA) is Data Centre World Asia’s Official Training Partner!
Data Centre World Asia, located in Singapore on the 29th & 30th October 2014, is largest, most influential gathering of data centre expertise ever assembled in Asia.
Data Centre World Asia includes an exhibition of 200 leading international suppliers as well as a world-class, case-study led conference programme with a number of dedicated theatres, containing 200 speakers and over 50 case studies focusing on best practice. All this practical content is worth $2000 SGD – and is available FREE of charge to SMA members who have this invitation.
Gain the latest insights from data centre thought-leaders, practitioners and visionaries including:
Johnson Tan, Director, Regional Head of Engineering Asia Pacific & Middle East, Barclays;
Anil Karmel, Co-Chair, National Institute of Standards and Technology;
Billy Lee Kok Chi, Chairman, Malaysian Data Centre Alliance;
David Blumanis, Vice President Data Centre Solutions and Key Account Management, Asia Pacific and Japan, IT Business, Schneider Electric;
Gavin O'Reilly, APAC Regional Head of Data Center Services, UBS;
Glenn Alann, Service Performance Manager Data Centres, National Bank of Australia;
Julian Kudritzki, COO, Uptime Institute;
Kris Holla, CSO, Data Center Products and Vice President, Nortek Inc., CES Group;
Manik Narayan, CIO – Asia Pacific & Japan, Global IT, SAP Asia Pacific;
Peter Rajaratnam, Head, Data Center Management, Prudential Services Asia to name a few...
Get practical advice from the 200 leading international suppliers including:
Dell, Huawei, Pacnet, Panduit, Kohler Power, Brocade, Digital Realty, Cicso, Mardix, TATA, SolidFire, Datwyler to name a few...
Whether you are already running and maintaining an advanced data centre, involved in initial projects or looking to improve or entirely re-shape your current data centre strategy, this is the one event you need to attend in 2014 – all completely FREE of charge.
Register now for your FREE tickets, worth over $2000 SGD at http://www.datacentreworldasia.com/SMA
Wednesday, July 30, 2014
Data Center Technical Visit
Again - Data Center Technical Visit
Sponsored by IXTech Limited
and Telehouse Hong Kong CCC (HKCOLO and KDDI Hong Kong)
We are pleased to announce that a Data Center Site Tour will serve for individuals who successfully attend our training seminars in Data Center Critical Facilities, Electrical and Air Conditioning System Design.
The Site Tour / Technical Visit targets to provide an interactive environment and opportunities for members of IDC industry to exchange professional views and experience on critical infrastructure and services.
It is also a rare chance to visit a world-class Tier III+ and a Tier II purpose-built data center facilities in Hong Kong during the same event.
For details, please visit the Site Tour Page and Rundown.
The Organizer
Strategic Media Asia (SMA) is one of the approved CPD course providers of the Chartered Institution of Building Services Engineers (CIBSE).
SMA is a critical infrastructure training, seminar and event organizer for corporations and professionals specialized in data center design & build, E&M facilities, structured cabling system, telecommunication, ICT and financial IT services.
For details of other data center courses and seminars, please visit our website at http://www.stmedia-asia.com/trainings.html.
Friday, July 25, 2014
Data Center Tier Levels and Uptime
The data center industry is laden with inter-related terms such as Uptime, Tier Levels, Availability, Redundancy and Reliability. In order to make an informed decision it is important to understand what they mean and what is the actual significance for any proposals you are considering in your analysis.
The concept of “Uptime” was pioneered by the Uptime Institute which was founded in 1993 and introduced its well defined Tier Classification system: I, II, III and IV, of which Tier IV represents the highest level of projected availability. Today, its Tier Certification system is globally recognized and its members are mostly Fortune 100-sized companies having multiple data centers averaging 50,000 square feet. And while not everyone subscribes to the Uptime Institute officially, marketing references to Tier 2,3 or 4 are common among those seeking to ascribe a certain level of design or construction to a data center’s overall availability or system redundancy, which may, or may not be totally accurate.
The terms “N, N+1 and 2N”, typically refer to the number of power and cooling components that comprise the entire data center infrastructure systems. Wherein “N” is the minimum rating of any component (such as a UPS, generator or cooling unit) required to support the critical load. An “N” system is not redundant at all, and the failure of any component will cause an outage, effectively describing a tier 1 type facility. N+1 and 2N, represent increasing levels of component redundancies and power paths, roughly mapping to the tiers 2-4, however it is important to understand that redundant components in themselves do not guarantee continuous availability, nor insure compliance with an Uptime Institute certified data center tier level.
Moreover, besides redundancy, the ability to do planned maintenance or emergency repairs on systems may involve the necessity to take them offline. This involves the key concept of “concurrent maintainability” which permits systems to be bypassed, without impacting the availability of the computing equipment. The Uptime Institute is well recognized in clearly defining concurrent maintainability in their Tier Level system. This is one of the key criteria in the design or certification of Tier III and Tier IV data centers.
Besides the level of infrastructure redundancy at the facility level, consistency of procedures for operations, maintenance and support of the critical infrastructure systems are key to ensuring continuous availability. Moreover, the Uptime Institute has now also established a related sub-category called Operational Sustainability to define and evaluate data center’s operational procedures, as an addition to their well recognized Tier Classification rating system.
Whether you chose to build or buy, you should examine all of these factors very closely to understand what is being promised if it is a brand new building and/or what the operating history of a proposed data center facility provider has been.
About Strategic Media Asia Limited
Strategic Media Asia (SMA) is one of the approved CPD course providers of the Chartered Institution of Building Services Engineers (CIBSE).
SMA, a critical infrastructure training and event organizer based in Hong Kong, provides an interactive environment and opportunities for members of IDC industry and engineers to exchange professional views and experience on critical infrastructure and E&M facilities.
For details of other data center courses and seminars, please visit our website at http://www.stmedia-asia.com/trainings.html.
The concept of “Uptime” was pioneered by the Uptime Institute which was founded in 1993 and introduced its well defined Tier Classification system: I, II, III and IV, of which Tier IV represents the highest level of projected availability. Today, its Tier Certification system is globally recognized and its members are mostly Fortune 100-sized companies having multiple data centers averaging 50,000 square feet. And while not everyone subscribes to the Uptime Institute officially, marketing references to Tier 2,3 or 4 are common among those seeking to ascribe a certain level of design or construction to a data center’s overall availability or system redundancy, which may, or may not be totally accurate.
The terms “N, N+1 and 2N”, typically refer to the number of power and cooling components that comprise the entire data center infrastructure systems. Wherein “N” is the minimum rating of any component (such as a UPS, generator or cooling unit) required to support the critical load. An “N” system is not redundant at all, and the failure of any component will cause an outage, effectively describing a tier 1 type facility. N+1 and 2N, represent increasing levels of component redundancies and power paths, roughly mapping to the tiers 2-4, however it is important to understand that redundant components in themselves do not guarantee continuous availability, nor insure compliance with an Uptime Institute certified data center tier level.
Moreover, besides redundancy, the ability to do planned maintenance or emergency repairs on systems may involve the necessity to take them offline. This involves the key concept of “concurrent maintainability” which permits systems to be bypassed, without impacting the availability of the computing equipment. The Uptime Institute is well recognized in clearly defining concurrent maintainability in their Tier Level system. This is one of the key criteria in the design or certification of Tier III and Tier IV data centers.
Besides the level of infrastructure redundancy at the facility level, consistency of procedures for operations, maintenance and support of the critical infrastructure systems are key to ensuring continuous availability. Moreover, the Uptime Institute has now also established a related sub-category called Operational Sustainability to define and evaluate data center’s operational procedures, as an addition to their well recognized Tier Classification rating system.
Whether you chose to build or buy, you should examine all of these factors very closely to understand what is being promised if it is a brand new building and/or what the operating history of a proposed data center facility provider has been.
About Strategic Media Asia Limited
Strategic Media Asia (SMA) is one of the approved CPD course providers of the Chartered Institution of Building Services Engineers (CIBSE).
SMA, a critical infrastructure training and event organizer based in Hong Kong, provides an interactive environment and opportunities for members of IDC industry and engineers to exchange professional views and experience on critical infrastructure and E&M facilities.
For details of other data center courses and seminars, please visit our website at http://www.stmedia-asia.com/trainings.html.